UNDERSTAND THE ESTIMATE
Try a checked example
A 15 × 20 ft room is 300 ft². The ENERGY STAR room-air-conditioner chart uses 7,000 BTU/h for the 250–300 ft² band before the listed sun, occupancy and kitchen adjustments. This is preliminary room-unit sizing, not a central-system load calculation.
Show all example inputs
| Units | US customary |
|---|---|
| Room length (ft) | 15 |
| Room width (ft) | 20 |
| Sun exposure | Normal |
| People who regularly use the room | 2 |
| The room is a kitchen | No |
- Preliminary cooling capacity (BTU/h): 7000
Illustrative project geometry and stated assumptions; not a product endorsement or construction specification.
Example checked on October 22, 2026. Calculation method and limits.
How to use the AC size calculator
- Measure the length and width of the room you want to cool.
- Choose the sun exposure. Heavily shaded rooms need less cooling and very sunny rooms need more.
- Enter how many people regularly use the room.
- Tick the kitchen box if the unit will cool a kitchen, which produces extra heat.
ENERGY STAR sizing chart
| Area to cool | Capacity |
|---|---|
| 100–150 sq ft | 5,000 BTU/h |
| 150–250 sq ft | 6,000 BTU/h |
| 250–300 sq ft | 7,000 BTU/h |
| 300–350 sq ft | 8,000 BTU/h |
| 350–400 sq ft | 9,000 BTU/h |
| 400–450 sq ft | 10,000 BTU/h |
| 450–550 sq ft | 12,000 BTU/h |
| 550–700 sq ft | 14,000 BTU/h |
| 700–1,000 sq ft | 18,000 BTU/h |
| 1,000–1,200 sq ft | 21,000 BTU/h |
| 1,200–1,400 sq ft | 23,000 BTU/h |
| 1,400–1,500 sq ft | 24,000 BTU/h |
| 1,500–2,000 sq ft | 30,000 BTU/h |
| 2,000–2,500 sq ft | 34,000 BTU/h |
Adjustments from the same ENERGY STAR guidance:
- Heavily shaded room: reduce capacity by 10%.
- Very sunny room: increase capacity by 10%.
- More than two people: add 600 BTU/h for each additional person.
- Kitchen: add 4,000 BTU/h.
Source: ENERGY STAR room air conditioners.
Worked example
A 15 × 20 ft bedroom (300 sq ft) used by two people:
- The chart gives 7,000 BTU/h.
- If the room is very sunny: 7,000 × 1.1 = 7,700 BTU/h, so pick the next common size up.
Why size matters
- An undersized unit runs constantly and still cannot keep the room cool.
- An oversized unit cools quickly but switches off before removing enough humidity, leaving the room cold and clammy.
- 1 ton of cooling equals 12,000 BTU/h, and 1 kW is about 3,412 BTU/h.
Calculation basis, defaults & source review
What this model calculates
Use the ENERGY STAR room-area band; apply ±10% sun/shade, then 600 BTU/h per occupant beyond two and 4000 BTU/h for a kitchen.
Fixed assumptions and limits
- Chart scope: 100–2500 ft²; 8 ft ceiling basis. Outside the range a full load assessment is needed.
- Band endpoints: Upper endpoint included by this calculator. At a shared boundary the source wording overlaps; this convention is explicit.
Cooling capacity is heat removal, not electrical input. This is not a full building load calculation.
Reset inputs for comparison
These are starting values, not a prescription or a record of your current inputs. Your estimate and exported report show the values actually used. Select a matching manufacturer reference or enter exact product data where supported.
| Parameter | US reset / unit | Metric reset / unit | Status |
|---|---|---|---|
| Room length | 15 ft | 4 m | Illustrative project input; not a prescribed value |
| Room width | 20 ft | 5 m | Illustrative project input; not a prescribed value |
| Sun exposure | Normal | Normal | Illustrative project input; not a prescribed value |
| People who regularly use the room | 2 | 2 | Illustrative project input; not a prescribed value |
| The room is a kitchen | No | No | Illustrative project input; not a prescribed value |
Evidence and applicability
- ENERGY STAR room air conditioner sizing — Web chart checked 22 October 2026. 100–2500 ft² chart based on 8 ft ceilings; shade/sun ±10%, 600 BTU/h per occupant beyond two, kitchen +4000 BTU/h. Review status: primary chart reviewed.
- NIST — revised unit conversion factors — International foot definitions; web reference checked 22 October 2026. Unit definitions and conversion factors only; not material density or product coverage. Review status: primary content reviewed.
Arithmetic, model and source-scope review: 22 October 2026. Indexed-only or access-limited sources are identified explicitly. Review does not verify your measurements, every product or every possible input. Independent professional engineering approval has not been obtained.
Sources and technical limitations
The ENERGY STAR room-air-conditioner table is the basis for the area bands. It is not a substitute for a complete building load calculation or a guarantee that a particular unit suits the room.
- ENERGY STAR room air conditioner sizing — Web chart checked 22 October 2026
100–2500 ft² chart based on 8 ft ceilings; shade/sun ±10%, 600 BTU/h per occupant beyond two, kitchen +4000 BTU/h. Review: primary chart reviewed.
- NIST — revised unit conversion factors — International foot definitions; web reference checked 22 October 2026
Unit definitions and conversion factors only; not material density or product coverage. Review: primary content reviewed.
Frequently asked questions
How many BTU do I need for a 12 × 12 room?
A 12 × 12 room is 144 sq ft, which falls in the 100–150 sq ft range, so about 5,000 BTU/h under normal conditions.
How many BTU do I need for 500 square feet?
500 sq ft falls in the 450–550 sq ft range, so about 12,000 BTU/h, before adjustments for sun, people or a kitchen.
What is 12,000 BTU in tons and kW?
12,000 BTU/h is 1 ton of cooling, or about 3.5 kW.
Can I use this for central air conditioning?
No. This chart is for room air conditioners. Central systems should be sized with a full load calculation, such as ACCA Manual J, done by an HVAC professional.